MCS100E CD
|
|
| |
Emission monitoring with very small measuring ranges The MCS100E CD is an analyzing system for extractive measurement of up to 8 IR-active gas compounds. It can be supplemented with oxygen and FID analyzers. The gas is dried by an integrated gas cooler thereby very small measuring ranges can be realized, especially for SO2, NO and NO2. Applications
- Flue gas monitoring in power stations
- Monitoring of combustion plants
- Emission monitoring of most different industrial plants
|
|
 |
 |
 |
 |
 |
Technical specification |
 |
 |
| |
Analyzer |
|
MCS100E |
|
 |
 |
 |
| |
Measuring principle |
|
Gas filter correlation, interference filter correlation, zirconium dioxide sensor |
|
 |
 |
 |
| |
Measuring components |
|
CH4, CO, CO2, H2O, N2O, NO, NO2, O2, SO2 |
|
 |
 |
 |
| |
Number of measuring components |
|
8 |
|
 |
 |
 |
| |
Measuring ranges |
|
CH4: 0 ... 100 mg/m³
CO: 0 ... 50 mg/m³
CO2: 0 ... 25 Vol%
H2O: 0 ... 5 Vol%
N2O: 0 ... 100 mg/m³
NO: 0 ... 50 mg/m³
NO2: 0 ... 80 mg/m³
O2: 0 ... 21 Vol%
SO2: 0 ... 10 mg/m³ |
|
 |
 |
 |
| |
Sample gas flow |
|
200 ... 1,000 l/h, depends on application |
|
 |
 |
 |
| |
Sample gas temperature |
|
Inlet analyzer system: 0 ... 220 °C (32 ... 428 °F)
In the process: 0 ... 1,300 °C (32 ... 2,372 °F) |
|
 |
 |
 |
| |
Sample gas pressure |
|
900 ... 1,100 hPa, atmospheric |
|
 |
 |
 |
| |
Ambient temperature |
|
5 ... 35 °C (41 ... 95 °F) |
|
 |
 |
 |
| |
Ambient pressure |
|
900 ... 1,100 hPa |
|
 |
 |
 |
| |
Conformities |
|
GOST, MCERTS |
|
 |
 |
 |
| |
Electrical safety |
|
CE |
|
 |
 |
 |
| |
Enclosure rating |
|
IP 43 |
|
 |
 |
 |
| |
Analogue outputs |
|
4 outputs:
0/4 ... 20 mA, 500 Ohm
Max. 64 outputs with opto box via optical fibre possible |
|
 |
 |
 |
| |
Analogue inputs |
|
4 inputs:
0/4 ... 20 mA
Max. 64 inputs with opto box via optical fibre possible |
|
 |
 |
 |
| |
Digital outputs |
|
12 outputs:
40 V, 1 A
Max. 64 outputs with opto box via optical fibre possible |
|
 |
 |
 |
| |
Digital inputs |
|
4 inputs:
50 V AC, 4 A / 24 V DC, 4 A
Max. 64 inputs with opto box via optical fibre possible |
|
 |
 |
 |
| |
Interfaces |
|
RS-232, RS-485
(Additional interfaces on request) |
|
 |
 |
 |
| |
Bus protocol |
|
MODBUS (Additional busses on request) |
|
 |
 |
 |
| |
System components |
|
Analyzer MCS100E, analyzer cabinet, sampling probe, sample gas cooler, sample gas line, sample gas pump |
|
 |
 |
 |
| |
|
|
|
|
 |
|
 |
|