MCS100E HW
|
|
| |
Emission and raw gas monitoring - also with high acid dew pointmeasuring ranges The MCS100E HW is an analyzing system for extractive measurement of up to 8 IR-active gas compounds. It can be supplemented with oxygen and FID analyzers. From sampling probe to cell, all components that are in contact with the sample gas are heated to above the dew point and thus protected from corrosion. This hot measurement technique allows the measurement of the water soluble components HCl and NH3. Applications
- Emission monitoring of waste incineration plants
- Monitoring of combustion plants with secondary fuels
- Process gas monitoring in cement plants
- Emission monitoring of refineries
- Emission monitoring of heavy oil fired diesel engines
|
|
 |
 |
 |
 |
 |
Technical specification |
 |
 |
| |
Analyzer |
|
MCS100E |
|
 |
 |
 |
| |
Measuring principle |
|
Gas filter correlation, interference filter correlation, zirconium dioxide sensor |
|
 |
 |
 |
| |
Measuring components |
|
CH4, CO, CO2, H2O, HCl, N2O, NH3, NO, NO2, O2, SO2 |
|
 |
 |
 |
| |
Number of measuring components |
|
8 |
|
 |
 |
 |
| |
Measuring ranges |
|
CH4: 0 ... 100 mg/m³
CO: 0 ... 75 mg/m³
CO2: 0 ... 25 Vol%
H2O: 0 ... 40 Vol%
HCl: 0 ... 15 mg/m³
N2O: 0 ... 100 mg/m³
NH3: 0 ... 20 mg/m³
NO: 0 ... 200 mg/m³
NO2: 0 ... 100 mg/m³
O2: 0 ... 21 Vol%
SO2: 0 ... 75 mg/m³ |
|
 |
 |
 |
| |
Sample gas flow |
|
200 ... 1,000 l/h, depends on application |
|
 |
 |
 |
| |
Sample gas temperature |
|
Inlet analyzer system: 0 ... 220 °C (32 ... 428 °F)
In the process: 0 ... 1,300 °C (32 ... 2,372 °F) |
|
 |
 |
 |
| |
Sample gas pressure |
|
900 ... 1,100 hPa, atmospheric |
|
 |
 |
 |
| |
Ambient temperature |
|
5 ... 35 °C (41 ... 95 °F) |
|
 |
 |
 |
| |
Ambient pressure |
|
900 ... 1,100 hPa |
|
 |
 |
 |
| |
Conformities |
|
2000/76/EC, 2001/80/EC, GOST, MCERTS, U.S. EPA compliant |
|
 |
 |
 |
| |
Electrical safety |
|
CE |
|
 |
 |
 |
| |
Enclosure rating |
|
IP 43 |
|
 |
 |
 |
| |
Analogue outputs |
|
4 outputs:
0/4 ... 20 mA, 500 Ohm
Max. 64 outputs with opto box via optical fibre possible |
|
 |
 |
 |
| |
Analogue inputs |
|
4 inputs:
0/4 ... 20 mA
Max. 64 inputs with opto box via optical fibre possible |
|
 |
 |
 |
| |
Digital outputs |
|
12 outputs:
40 V, 1 A
Max. 64 outputs with opto box via optical fibre possible |
|
 |
 |
 |
| |
Digital inputs |
|
4 inputs:
50 V AC, 4 A / 24 V DC, 4 A
Max. 64 inputs with opto box via optical fibre possible |
|
 |
 |
 |
| |
Interfaces |
|
RS-232, RS-485
(Additional interfaces on request) |
|
 |
 |
 |
| |
Bus protocol |
|
MODBUS (Additional busses on request) |
|
 |
 |
 |
| |
System components |
|
Analyzer MCS100E, analyzer cabinet, sampling probe, sample gas line, sample gas pump |
|
 |
 |
 |
| |
|
|
|
|
 |
|
 |
|