Search   Start
 
FLOWSIC100 PR
 
 
Gas Flow Measurement for Continuous Emission Monitoring
FLOWSIC100 -The reliable and precise flow measurement with highest demands on durability
The device type FLOWSIC100 PR is conceived for stack diameters greater than 0.4 m (1.31 ft). The construction as a probe type with two transducers is best suitable for the stack installation from one side only.
This device is certificated according to 2001/80/EC, 2000/76/EC, 27th BImSchV (Federal Immission Control Ordinance) as well as TA air.
Areas of application
Power generation (e. g. power plants), processing industries (cement manufacturing, steel and iron production), waste disposal industry (e. g. waste incineration plants), chemical industry, petrochemical plants and refineries, pulp, paper and textile industry, ventilation and heating plants
 
Technical specification
    Sender/Receiver Unit  
  Measuring values   Gas velocity in m/s (ft/s), volume flow in m³/h (ft³/h) operation and standard state, temperature in °C (°F)  
  Measurement principle   Ultrasonic propagation time delay measurement  
  Measuring range   0 ... +/- 40 m/s (0 ... +/-131 ft/s)  
  Measuring section   0.27 ... 0.28 m (0.89 ... 0.92 ft), fix  
  Inner channel diameter   > 0.4 m (> 1.31 ft)  
  Gas temperature   -40 ... +260 °C (-40 ... +500 °F)  
  Mounting angle   45°  
  Channel internal pressure   -100 ... +100 hPa (-1450 ... +1450 PSI)  
  Max. dust loading   1 g/m³ (0.4370 gr/ft³)  
  Ambient temperature   Sender/Receiver unit: -40 ... +60 °C (-40 ... +140 °F)
Control unit: -40 ... +60 °C (-40 ... +140 °F)
 
  Protection category   IP 65  
    Control Unit MCU  
  Analog output signals   0/2/4 ... 22 mA, max. 750 ohm apparent ohmic resistance, 12 bit resolution
option: more analog outputs via additional I/O-modules
 
  Analog input signals   2 inputs 0 ... 5/10 V or 0/2/4 ... 22 mA (without galvanic isolation), 10 bit resolution  
  Digital output signals   5 potential-free relais outputs (changers) for status signals operating/malfunction, limit value, warning, maintenance, control cycle
option: more digital outputs via additional I/O-modules
 
  Digital input signals   4 potential-free contacts for link to maintenance switch, actuate control cycle, separate zero-point monitoring, separate span test  
  Interfaces   USB 1.1, RS232  
  Buses   option: Profibus, Ethernet  
     
Shopping Cart
Info service